Conduit Fill: PVC

Conduit Fill Chart

The following is a typical PVC conduit fill chart, which show how many wires can safely fit into a PVC conduit. The possible wire gauges range from 14 AWG to 1000 MCM, and from conduit trade sizes of 1/2 inches to 6 inches.

Trade Size in InchesWire Size (THWN, THHN) Conductor Size AWG/kcmil
1412108643211/02/03/04/02503003504005006007007501000
1/2
1/2 in. SCH 4011853111111
1/2 in. SCH 8096421111
3/4
3/4 in. SCH 40211595421111111
3/4 in. SCH 8017127431111111
1
1 in. SCH 403425159643311111111
1 in. SCH 8028201375332111111
1 1/4
1 1/4 in. SCH 40604327161176533211111111
1 1/4 in. SCH 805137231396543211111111
1 1/2
1 1/2 in. SCH 4082593721159875433211111111
1 1/2 in. SCH 8070513218138764331`11111111
2
2 in. SCH 401359962362616131187654332111111
2 in. SCH 801188654312214121076543321111111
2 1/2
2 1/2 in. SCH 401931418951372219161210876443321111
2 1/2 in. SCH 80170124784532201714109765533321111
3
3 in. SCH 402992181377957353025181513119765543321
3 in. SCH 80265193122705131262216141198655433221
3 1/2
3 1/2 in. SCH 404012931841067747403325211714121087654433
3 1/2 in. SCH 8035826116495684235302218151310876654332
4
4 in. SCH 4051737723813799615143322722181512119875543
4 in. SCH 804643382131238954463929242017141198765443
5
5 in. SCH 40815594374216156968168504235292420171513119876
5 in. SCH 80736537338195141867361453832262218151312108775
6
6 in. SCH 40>1K85954131222513811798736151423528242119161311118
6 in. SCH 80>1K7704852792021241058865554638312522191714121097